Victaulic Catalog
IPS Copper Tubing
Grooved Piping System
| Tubing - In./mm | Type "K" - ASTM B-88 | Type "L" - ASTM B-88 | |||||
| Nom. Size | Act. Size | Wall Thick. Inches mm | Max. Joint Wk. Press. PSI/kPa | Max. Permis. End Load Lbs./N | Wall Thick. Inches. mm | Max. Joint Wk. Press. PSI/kPa | Max. Permis. End Load Lbs./N |
| 2 50 | 2.125 54.0 | 0.083 2.1 | 300 2065 | 1,065 4740 | 0.070 1.8 | 300 2065 | 1,065 4740 |
| 2 1/2 65 | 2.625 66.7 | 0.095 2.4 | 300 2065 | 1,625 7230 | 0.080 2.0 | 300 2065 | 1,625 7230 |
| 3 80 | 3.125 79.4 | 0.109 2.8 | 300 2065 | 2,300 10235 | 0.090 2.3 | 300 2065 | 2,300 10235 |
| 4 100 | 4.125 104.8 | 0.134 2.8 | 300 2065 | 4,005 17825 | 0.110 2.8 | 300 2065 | 4,005 17825 |
| 5 150 | 5.125 130.2 | 0.160 4.1 | 300 2065 | 6,190 27550 | 0.125 3.2 | 300 2065 | 6,190 27550 |
| 6 150 | 6.125 155.6 | 0.192 4.9 | 300 2065 | 8,840 39340 | 0.140 3.6 | 300 2065 | 8,840 39340 |
| 8 200 | 8.125 206.4 | 0.271 6.9 | 300 2065 | 15,550 69200 | 0.200 5.1 | 300 2065 | 15,550 69200 |
| Tubing Inches/mm | Type "M" ASTM B-88 | DMV ASTM B-306 | |||||
| Nom. Size | Act. Size | Wall Thick. In. mm | Max. Joint Wk. Press. PSI/kPa | Max. Permis. End Load Lbs./N | Wall Thick. Inch. mm | Max. Joint Wk. Press. PSI/kPa | Max. Permis. End Load Lbs./N |
| 2 50 | 2.125 54.0 | 0.058 1.5 | 250 1725 | 890 3960 | - - | - - | - - |
| 2 1/2 65 | 2.625 66.7 | 0.065 1.7 | 250 1725 | 1,350 6010 | - - | - - | - - |
| 3 80 | 3.125 79.4 | 0.072 1.8 | 250 1725 | 1,415 6300 | 0.045 1.1 | 100 690 | 765 3405 |
| 4 100 | 4.125 104.8 | 0.095 2.4 | 250 1725 | 3,340 14865 | 0.058 1.5 | 100 690 | 1,335 5940 |
| 5 150 | 5.125 130.2 | 0.109 2.8 | 200 1375 | 4,125 18360 | 0.072 1.8 | 100 690 | 2,060 9170 |
| 6 200 | 6.125 155.6 | 0.122 3.2 | 200 1375 | 5,890 26210 | 0.083 2.1 | 100 690 | 2,945 13105 |
| 8 200 | 8.125 206.4 | 0.170 4.3 | 200 1375 | 10,370 46100 | 0.109 2.8 | 100 690 | 5,180 23000 |
Working Pressure and End Load are total, from all internal and external loads, based on copper tubing of the weight indicated, standard roll grooved in accordance with victaulic specifications. Contact Victaulic for performance on other pipe.
No. 610, No. 611 &
No. 620
Elbows and Tee
![]() | ![]() | ![]() |
| Tubing Inches/mm | No. 610 90° Elbow | No. 611 45° Elbow | No. 620 Tee | ||||
| Nom. Size | Actuall Size | C to E Inches mm | Aprx. Wgt. Ea. Lbs./kg | C to E Inches mm | Aprx. Wgt. Ea. Lbs./kg | C to E Inches mm | Aprx. Wgt. Ea. Lbs./kg |
| 2 50 | 2.125 54.0 | 2.91 74 | 0.9 0.4 | 2.19 56 | 0.8 0.4 | 2.69 62 | 1.1 0.5 |
| 2 1/2 65 | 2.625 66.7 | 3.31 84 | 1.3 0.6 | 2.31 59 | 1.1 0.5 | 3.20 81 | 1.8 0.8 |
| 3 80 | 3.125 79.4 | 3.81 97 | 2.1 1.0 | 2.59 66 | 1.6 0.7 | 3.52 89 | 3.2 1.5 |
| 4 100 | 4.125 104.8 | 4.75 121 | 4.0 1.8 | 3.19 81 | 3.4 1.5 | 4.25 108 | 6.1 2.8 |
| 5 125 | 5.125 130.2 | 5.94 151 | 15.0 6.8 | 3.25 83 | 10.0 4.5 | 5.94 151 | 18.5 8.4 |
| 6 150 | 6.125 155.6 | 6.94 176 | 20.0 9.1 | 3.50 89 | 13.0 5.9 | 6.94 176 | 25.5 11.6 |
| 8 200 | 8.125 206.4 | 7.75 197 | 26.0 11.8 | 4.25 108 | 15.6 7.1 | 7.75 197 | 45.0 20.4 |
Victaulic copper fittings are full-flow, standard radius fittings, supplied roll grooved, and are available in
configurations which include elbows, tees, groove-by-groove and groove-by-cup reducers.
Request 22.04.