Victaulic Catalog

IPS Carbon Steel Pipe
Grooved Couplings


Style 78
Snap-Joint Coupling

Nom.
Size
In./mm
Max.
Work
Pres.
PSI
*
kPa
Dimensions
Inches/mm
Aprx.
Wgt.
Each
Lbs.
kg
Y Z
1
25
300
2065
3.25
83
1.75
44
0.8
0.4
1 1/4
32
300
2065
3.75
95
1.75
44
1.1
0.5
1 1/2
40
300
2065
4.75
121
1.75
44
1.7
0.8
2
50
300
2065
4.75
121
1.75
44
1.8
0.8
2 1/2
65
300
2065
5.88
149
1.75
44
2.5
1.1
3
80
300
2065
6.25
159
1.75
44
3.0
1.4
4
100
300
2065
7.75
197
2.00
51
5.4
2.5
5
125
300
2065
9.50
241
2.00
51
9.8
4.4
6
150
300
2065
10.50
267
2.00
51
11.4
5.2
8
200
300
2065
13.00
330
2.38
60
15.3
6.9

* Click here for notes.
Refer to Victaulic Pocket Handbook I-100 for special safety cautions when used for concrete pumping.

Style 78 Snap-Joint couplings are designed for quick disconnect service. Mated housing are hinged with an attached locking handle for assembly. Housings through 4" (100 mm) size have a smooth outer surface. Larger sizes have cross-ribbed design for added strength.


Style 775
Coupling for Plastic Pipe

Nom.
Size
In.
mm
Max.
Work
Pres.
PSI
*
kPa
Dimensions
Inches/mm
Aprx.
Wgt.
Each
Lbs.
kg
Nom.
Size
In.
mm
Max.
Work
Pres.
PSI
*
kPa
Dimensions
Inches/mm
Aprx.
Wgt.
Each
Lbs.
kg
Y Z Y Z
2
50
* 5.13
130
2.19
56
1.7
0.8
6
150
* 11.00
279
3.06
78
8.0
3.6
2 1/2
65
* 5.88
149
2.63
68
2.1
1.0
8
200
* 14.00
356
3.31
84
13.7
6.2
3
80
* 6.75
172
2.50
64
2.7
1.2
10
250
* 16.50
419
3.63
92
19.6
8.9
4
100
* 8.00
203
2.63
68
3.6
1.6
12
300
* 19.00
483
3.38
86
24.0
10.9

* For Victaulic Coupling Performance and Pressure Ratings for PVC Pipe refer to 20.03.
NOTE: Generally not recommended for use on systems operating at greater than + 100°F (+38°C). Contact Victaulic for recommendation on service from +100°F to +140°F (+38°C to +60°C).

Click here for notes.

Style 775 couplings are designed specifically for use on radius cut grooved or standard roll grooved rigid plastic pipe. The housing is designing with "wing" extensions to increase joint strength by reducing stress concentration at the groove/key engagement and transferring it to the full wall of the pipe body.
Request 20.01