Victaulic Catalog

IPS Carbon Steel Pipe
Fit System


Fit Piping System for Steel Pipe

The FIT (Fast Installation Technique) line of products is designed specifically to join plain end steel pipe withoutthreading or welding (pipe ends must be properly cleaned). The unique locking lug secures pipe to the FIT fittings with just a quarter-turn. Gaskets, located in both ends of the fittings, seal as the pipe is inserted past them and sealing is enhanced by pressure in the line. Silicone gaskets are recommended for fire protection dry systems, all systems operating below 0°F (-17°C).
Internal pipe stops provide a uniform take-out dimension. Marking of the pipe indicates correct insertion of the pipe to the stop. Visual locking indicator cast into the housing corresponds to lug markings for visual verification of the lug locked position.
FIT products ate UL, ULC and FM rated for 175 PSI (1200 kPa) working pressure on Schedule 10/40 steel pipe.They are approved and listed for above ground fire protection systems, automatic sprinkler, open sprinkler and standpipe both wet and dry systems Electrogalvanized housings are available and recommended for special hazards, exposed locations and corrosive environments.
Request 13.01.


Performance Data

Pipe
Inches
millimeters
Commercial DataFire Protection
UL/ULC/FM Approved
Schedule 40, 10, XL
*
Schedule 10Schedule 40
Nominal
Size
Actual
Size
Max.
Work
Press.
PSI
kPa
Max.
Perm
End Load
Lbs.
N
Max.
Work
Press.
PSI
kPa
Max.
Perm.
End Load
Lbs.
N
Max.
Work
Press.
PSI
kPa
Max.
Perm.
End Load
Lbs.
N
1
25
1.315
33.4
250
1725
335
1490
350
2410
470
2090
175
1200
235
1045
1 1/4
32
1.600
42.4
250
1725
540
2400
350
2410
750
3337
175
1200
375
1668
1 1/2
40
1.900
48.3
250
1725
775
3448
350
2410
1080
4806
175
1200
540
2403
2
50
2.375
60.3
250
1725
110
4895
350
2410
1550
6897
175
1200
775
3448

§ UL/ULC/FM working pressure based upon 5 to 1 test to rated pressure formula.
* UL Listed (only) for use on "XL" pipe. (Victaulic FIT pipe tolerances - below apply).


Flow Data

Victaulic FIT (Fast Installation Technique) products have been flow tested and provide flow performance equivalent or superior to comparable threaded components.


Pipe Tolerances

Pipe (Schedule 10 - 40 steel) for use with FIT products must conform to the tolerances listed in the chart and must conform to the standards of "Acceptability."

Inches/millimeters
SizeNom. O.D.Max. O.D.Min. O.D.
1
25
1.315
33.4
1.325
33.7
1.297
32.9
1 1/4
32
1.660
42.2
1.670
42.4
1.642
41.7
1 1/2
40
1.900
48.3
1.910
48.5
1.882
47.8
2
50
2.375
60.3
2.385
60.6
2.357
59.9