Victaulic Catalog
IPS Carbon Steel Pipe
Fire Protection Products
Style 744
FireLock Flange Adapter
![]() | ![]() |
| Nom. Size In. mm | Max. Work Pres. PSI* kPa | Dimensions Inches/mm | Aprx. Wgt. Ea. Lbs. kg | Nom. Size In. mm | Max. Work Pres. PSI* kPa | Dimensions Inches/mm | Aprx. Wgt. Ea. Lbs. kg | ||
| W | X | W | X | ||||||
| 2 50 | 175 1200 | 6.75 172 | 6.00 152 | 2.7 1.2 | 5 125 | 175 1200 | 11.00 279 | 10.00 254 | 8.3 3.8 |
| 2 1/2 65 | 175 1200 | 7.88 200 | 7.00 178 | 4.2 1.9 | 6 150 | 175 1200 | 12.00 305 | 11.00 279 | 9.3 4.2 |
| 3 80 | 175 1200 | 8.44 214 | 7.50 191 | 4.8 2.2 | 8 200 | 175 1200 | 14.63 372 | 13.50 343 | 13.9 6.3 |
| 4 100 | 175 1200 | 9.94 252 | 9.00 229 | 7.1 3.2 | |||||
Because of the outside flange dimension, FireLock Flange adapters should not be used
on FireLock fittings. When wafer or lug-type valves are used adjoining a Victaulic fitting,
check disc dimensions to assure proper clearance.
FireLock Flange adapters should not be used as anchor points for tie-rods across
nonrestrained joints. Mating rubber faced flanges, valves, etc., require the use of a
FireLock Flange washer.
FireLock Flange gaskets must always be assembled with the color coded lip on the pipe
and the other lip facing the mating flange.
See Vic-Flange Adapter Notes, click here for info.
Style 744
Sealing Surface
| Nominal Size In. mm | Sealing Surface Inches/mm | Nominal Size In. mm | Sealing Surface Inches/mm | ||
| "A" Max. | "B" Min. | "A" Max. | "B" Min. | ||
| 2 50 | 2.38 60 | 3.41 87 | 5 125 | 5.56 141 | 6.71 171 |
| 2 1/2 65 | 2.88 73 | 3.91 99 | 6 150 | 6.63 168 | 7.78 198 |
| 3 80 | 3.50 89 | 4.53 115 | 8 200 | 8.63 219 | 9.94 252 |
| 4 100 | 4.50 114 | 5.53 141 | |||