Victaulic Catalog

IPS Carbon Steel Pipe
Grooved Couplings


Style 741
Vic-Flange Adapter

ANSI Class 125 & 150 Flange
Sizes 2 - 12" (50 - 300 mm)


Note: Gray area of mating face must be free from gouges, undulations or deformities of any type for effective sealing.

Nom.
Size
In.
mm
Max.
Work
Pres.
PSI
*
kPa
Dimensions
Inches/mm
Aprx.
Weight
Each
Lbs.
kg
W Z
2
50
300
2065
6.75
172
0.75
19
3.1
1.4
2 1/2
65
300
2065
7.88
200
0.88
22
4.7
2.1
3
80
300
2065
8.44
214
0.94
24
5.4
2.4
4
100
300
2065
9.94
252
0.94
24
7.7
3.5
5
125
300
2065
11.00
279
0.94
24
9.3
4.2
6
150
300
2065
12.00
305
1.00
25
10.3
4.7
6 1/2 §§ 300
2065
+ 1.00
25
10.0
4.5
8
200
300
2065
14.63
372
1.13
29
16.6
7.5
10
250
300
2065
17.19
437
1.19
30
24.2
11.0
12
300
300
2065
20.25
514
1.25
32
46.8
21.2

*Click here for notes.
§§ See notes below
+ Contact Victaulic for details.

Style 741 Vic-Flange adapter is designing for directly incorporating flanged components with ANSI CL, 125 or CL. 150 bolt hole patterns into a grooved pipe system. Sizes 2 - 12" (50 - 300 mm) are hinged for easy handling with integral end tabs which facilitate assembly.
Request 06.06.


Style 741
Vic-Flange Adapter

ANSI Class 125 & 150 Flange
Sizes 14 - 24" (350 - 600 mm)

Note: Gray area of mating face must be free from gouges, undulations or deformities of any type for effective sealing.

Nom.
Size
In.
mm
Max.
Work.
Pres.
PSI
*
kPa
Dimensions
Inches/mm
Aprx.
Wgt.
Each
Lbs.
kg
W Z
14
350
300
2065
24.50
622
1.44
37
75.0
34.0
16
400
300
2065
27.12
689
1.44
37
90.0
40.8
18
450
300
2065
29.00
737
1.56
40
100.0
45.4
20
500
300
2065
31.50
800
1.69
43
120.0
54.4
24
600
300
2065
36.00
914
1.94
49
160.0
72.6

* Click here for notes.
See notes below.

Style 741 Vic-Flange adapter is designing for directly incorporating flanged components with ANSI CL, 125 or CL. 150 bolt hole patterns into a grooved pipe system. Sizes 14 - 24" (350 - 600 mm) are cast in four (4) identical segments which are interconnected as assembly is completed.
Request 06.06.


Style 743
Vic-Flange Adapter

Grooved pipe adapter to
ANSI Class 300 flanges

Note: Gray area of mating face must be free from gouges, undulations or deformities of any type for effective sealing.

Nom.
Size
In.
mm
Max.
Wk.
Pres.
PSI
*
kPa
Dimensions
Inches/mm
Aprx.
Wgt.
Each
Lbs.
kg
X Z
2
50
720
4960
6.50
165
0.94
24
4.8
2.2
2 1/2
65
720
4960
7.50
191
1.06
27
7.4
3.4
3
80
720
4960
8.25
210
1.19
30
9.1
4.1
4
100
720
4960
10.00
254
1.31
33
15.3
6.9
5
125
720
4960
11.00
279
1.44
25
17.7
8.0
6
150
720
4960
12.50
318
1.50
38
23.4
10.6
8
200
720
4960
15.00
381
1.69
43
34.3
15.6
10
250
720
4960
17.50
445
1.94
49
48.3
21.9
12
300
720
4960
20.50
521
2.00
51
70.5
32.0

* Click here for notes.
See notes below.

Vic-Flange Style 743 flange-to-groove adapter permits direct connection of ANSI Class 300 raised face flanged components. It can be used with flat-face flanges by removing the raised projections on the outside face of the flange.
Request 06.06.


Vic-Flange Adapter
Sealing Surface

Nom.
Size
In.
mm
Sealing Surface
Inches/mm
Nom.
Size
In.
mm
Sealing Surface
Inches/mm
Nom.
Size
In.
mm
Sealing Surface
Inches/mm
"A"
Max.
"B"
Min.
"A"
Max.
"B"
Min.
"A"
Max.
"B"
Min.
2
50
2.38
60
3.41
87
6
150
6.63
168
7.78
198
14
350
14.00
356
16.39
416
2 1/2
65
2.88
73
3.91
99
6 1/2 §§ 6.50
165
7.66
195
16
400
16.00
406
18.39
467
3
80
3.50
89
4.53
115
8
200
8.63
219
9.94
252
18
450
18.00
457
20.00
508
4
100
4.50
114
5.53
141
10
250
10.75
273
12.31
313
20
500
20.00
508
22.50
572
5
125
5.56
141
6.71
171
12
300
12.75
324
14.31
364
24
600
24.00
610
27.75
705

VIC-FLANGE ADAPTER NOTES

§§ O.D. Dimension
Style 743 Vic-Flange must be ordered as a factory assembly when connected to a Victaulic fitting or valve. ContactVictaulic for details
Bolts required to be supplied by installer, may be ordered from Victaulic. Bolt sizes for conventional flange-to-flange connection. Longer bolts required when Vic-Flange is utilized with wafer-type valves.
Draw bolts supplied with 14 - 24" (350 - 600 mm) Vic-Flange adapters
IMPORTANT NOTES: Style 741 Vic-Flange adapters provide rigid joints when used on pipe with standard cut or roll groove dimensions and consequently allow no linear or angular movement at the joint. When used with Victaulic Series 700 butterfly valves, plastic pipe or light wall metallic pipe, small teeth in I.D. of key section should be removed and may be used on one side of the valve. Contact Victaulic for information on AS2129 - Table E; ISO 2084 (PN10); DIN 2532 (PN10) and JIS B-2210 (10K) flanges.
Because of the outside flange dimension, Vic-Flange should not be used within 90° of one another on a standard fitting. When wafer or lug-type valves are used adjoining a Victaulic fitting, check disc dimensions to assure proper clearance.
Vic-Flange adapters should not be used as anchor points for tie-rods across non-restrained joints. Mating rubber faced flanges, valves, etc., require the use of a Vic-Flange washer. Vic-Flange gaskets must always be assembled with the color coded lip on the pipe and the other lip facing the mating flange.